- Joist (floor/roof) : C24 minimum
Any element whose strength class is below the required minimum is REJECTED
at qualification stage.
§2.2 â Moisture content (BS EN 1995-1-1 §2.3)
Timber moisture content at time of installation must be between 10% and 18%.
Below 10%: risk of excessive moisture uptake after installation.
Above 18%: risk of fungal development and differential shrinkage.
Any element with moisture content outside [10%, 18%] is REJECTED.
§2.3 â Allowable deflection (EC5 §7.2)
Instantaneous deflection under load must satisfy:
- Allowable deflection = L / 300 (L = span in mm)
- Minimum floor value: 5 mm over 2 m span
Any element whose measured deflection exceeds L/300 is REJECTED.
=============================================================================
§3 â FRAME GEOMETRY
=============================================================================
§3.1 â Stud spacing (BS EN 1995-1-1 §5.1)
Stud centre-to-centre spacing must be between 300 mm and 600 mm.
Standard values: 400 mm or 600 mm (± 5 mm tolerance).
Spacing exceeding 600 mm is non-compliant.
§3.2 â Minimum cross-sections for load-bearing studs (BS EN 1995-1-1 §5.2)
Minimum cross-sections depend on clear height and spacing:
- Height ⤠2700 mm, spacing ⤠400 mm : 38 à 89 mm minimum
- Height ⤠2700 mm, spacing ⤠600 mm : 38 à 140 mm minimum
- Height ⤠3000 mm, spacing ⤠400 mm : 38 à 140 mm minimum
- Height ⤠3000 mm, spacing ⤠600 mm : 44 à 140 mm minimum
- Height > 3000 mm, any spacing : 44 Ã 184 mm minimum
Cross-section is compliant if b ⥠b_min AND h ⥠h_min.
§3.3 â Minimum cross-sections for non-load-bearing studs
Non-load-bearing studs require a minimum cross-section of 38 Ã 63 mm,
regardless of clear height.
§3.4 â Continuity of load-bearing studs (BS EN 1995-1-1 §5.4)
A load-bearing stud must not contain a longitudinal splice (end-to-end joint
within the storey height). The presence of a longitudinal splice on a
load-bearing stud is a structural non-conformity.
=============================================================================
§4 â THERMAL PERFORMANCE AND VAPOUR CONTROL
=============================================================================
§4.1 â Minimum thermal resistance of insulation (Part L + BS EN ISO 6946)
Thermal resistance R is calculated as:
R = thickness (mm) / (1000 à lambda) [unit: m²·K/W]
lambda = thermal conductivity in W/(m·K)
Minimum R required by climate zone:
- Zone A (highland / severe cold) : R_min = 6.5 m²·K/W
- Zone B (temperate) : R_min = 4.5 m²·K/W
- Zone C (mild â coastal south) : R_min = 3.5 m²·K/W
Typical conductivity values:
- Mineral wool 035 : lambda = 0.035 W/(m·K)
- Mineral wool 040 : lambda = 0.040 W/(m·K)
- Rigid PIR 022 : lambda = 0.022 W/(m·K)
§4.2 â Vapour control layer: minimum Sd value (BS 5250 / BS EN ISO 13788)
The vapour control layer must provide sufficient resistance to vapour
diffusion (Sd value) according to the service class:
- Service class 1 (dry interior) : Sd ⥠5 m
- Service class 2 (humid interior) : Sd ⥠18 m
- Service class 3 (very humid) : Sd ⥠50 m
Any vapour control layer with Sd below the required minimum is NON-COMPLIANT.
=============================================================================
§5 â FIRE SAFETY
=============================================================================
§5.1 â Required fire resistance period (Building Regs Part B / BS EN 13501-2)
Structural elements must achieve a minimum fire resistance period:
- Single occupancy dwelling (non-collective) : REI 30 minimum
- Multi-occupancy building (collective = 1) : REI 60 minimum
§5.2 â Reaction to fire of internal lining (BS EN 13501-1)
The internal wall lining (typically plasterboard) must satisfy:
- Reaction to fire class: A1 or A2 minimum (Euroclasses)
- Surface mass: ⥠8 kg/m² (standard 12.5 mm or 15 mm plasterboard)
Any lining with a reaction class below A2 or insufficient mass is NON-COMPLIANT.
§5.3 â Plasterboard thickness (Building Regs Part B §B3)
To achieve the required fire resistance:
- REI 30 (non-collective) : plasterboard thickness ⥠12.5 mm
- REI 60 (collective) : plasterboard thickness ⥠25 mm (two layers)
=============================================================================
§6 â GLOBAL COMPLIANCE
=============================================================================
§6.1 â Compliance conditions by element type
An element is declared COMPLIANT if and only if all applicable conditions
for its type are satisfied:
For all elements : qualified = 'YES'
For structural elements (load-bearing studs, sole plates, top plates) :
+ frame_ok = 'YES'
For insulation and vapour control layers :
+ thermal_ok = 'YES'
For all elements if collective = 1 :
+ fire_ok = 'YES'
For all elements if collective = 0 :
fire_ok = 'YES' also required (REI 30 minimum applies)
§6.2 â Pipeline termination
The pipeline terminates (solved) when all elements carrying the slot
needs_compliance have received their compliance_status.